Pulaski County Energy Efficiency Community Block Grant
Projects
Fluorescent Lighting Retrofit
Government Services Building
45 S. Lumpkin St.
Newspaper November 2011 Quote Requests
The Government Services Building existing 4 bulb, 2 magnetic ballast fixtures used nearly 140 watts per hour, whether or not all the bulbs are functioning. Also utilizing a lower watt bulb doesn't reduce wattage as the wattage use is based on the draw of power determined by the magnetic ballast.
The newer T8 bulb fixture with electronic ballast is much more efficient at reducing energy cost.
The chart below compares the old T12 fixtures with magnetic ballast with the new T8 electronic ballast. (These valves were determined using a Kill-A-Watt meter)
|
Fixture |
Watts Used per Hour |
|
T8 fixture with 2 bulbs in use |
62 |
|
T8 fixture with 3 bulbs in use |
84 |
|
T12 fixture with 4 bulbs in use |
142 |
Wattage Usage Chart for 152 fluorescent fixtures
| watts/hr | rate (kw) | nr hours | cost | nr fixtures | total | |
| upgrade | 62 | 0.125 | 2000 | $15.50 | 110 | $1,705 |
| upgrade | 84 | 0.125 | 2000 | $21.00 | 42 | $882 |
| original | 142 | 0.125 | 2000 | $35.50 | 152 | $5,396 |
| approximate yearly savings - $2,809 | ||||||
| approximate yearly CO2 emission reduction - 15.24 metric tons | ||||||